160 kV To 500 kV Diesel Generators Page

Standard Diesel Generators

Pricing

Size

160kW

200kW

250kW

300kW

500kW

ALTERNATOR SPECIFICATIONS

TFW-160KW-4P

TFW-200KW-4P

TFW-250KW-4P

TFW-300KW-4P

TFW-500KW-4P

Rated Power (kW)

160

200

250

300

500

Rated Voltage (v)

120/240V or 220/380V or 347/300V

Rated Current (A)

481/304/193

6601/380/241

752/475/301

902/570/361

1504/950/601

Rated Frequency (HZ)

60

Rated Speed (rpm)

1800

Power Factor

0.8

Phase Connection

3-Phase, 4-Wire

Winding Connection

Star-connected

Excitation Method

Brushless

Insulation Method

F Class

Regulation Method

AVR

Steady-state Voltage regulation Rate

1%

Degree of Protection

IP23

ENGINE SPECIFICATIONS

 6135AD-1

12V135AD

12V135AD 

 12V135ZD

 12V190BD-2

Model

Four stroke, water-cooled, inline, direct injection diesel

Number of Cylinders

6

12

12

12

12

Total Displacement (L)

12.9

25.8

25.8 

28.5 

 

Fuel Consumption gr./kW.hr

232.6

240.6

240.6

 240.6

214

Run time @ 75% load

6

4.7 

3.7

3.1

2.1

Air Intake

Naturally Aspirated

Naturally Aspirated

Naturally Aspirated

Turbo Charged

Naturally Aspirated

Rated Output (hp)

264

360

465

 504

 900

Approx. Oil consumption

2.72 gr./kW.hr

Starting System

24V

UNIT

 

 

 

 

 

Dimension L x W x H (cm)

 350 x150 x220

380 x180 x220

380 x180 x220 

380 x180 x220 

610 x 204 x295

Dry Weight (kg)

3500

3650

 3950

4100 

14500

Decibels at 7 M.

85 - 87

Fuel Tank Capacity (L)

200

Protection Devices

Low Oil, High Water Temp., Over Speed, Overload

 Pricing

Power To Go   Return To Power To Go Main Page
Contact Information

F.Y.I. any top menu link will lead you back to a new cascading menu page.
Please submit comments, suggestions, problems or contact us with our
If the "Email Form" link is not displayed you must enable Java Script to access it!
No Utility Bills Inc. All rights reserved. Last modified: 10/19/24