Product & installation specifications are subject to change without notice.
Product installation must adhere strictly to the installation manual shipped with product!
The Kodiak 1200 and 1700 Flat & Step Top stoves require one of the following forms of
hearth protection if not installed directly on concrete poured on earth:
1) Any UL, ULC, or Warnock Hersey Listed Type 1 hearth board.
2) Any noncombustible material.
In Canada, floor protection must extend 18" from the front of the stove
and 8" from the sides and rear of the stove.
Straight Floor Protector
* Use appropriate column in chart as the
Kodiak 1200 and 1700 have different specs.
Example: Minimum straight floor protector for the Kodiak 1200 Flat & Step Top - 40-1/2"w x 46"d
Corner Floor Protector
* Use appropriate row in chart as the
Kodiak 1200 and 1700 have different specs.
Example: Minimum corner floor protector for the Kodiak 1200 Flat & Step Top - 59-7/8" x 56-5/8" x 28-1/8"